If you install or connect 3-phase motors and systems, you recognize the importance of verifying the correct motor rotation and wiring phase sequence. Improper connections can cause motors to rotate in reverse direction, potentially damaging the motor and the equipment it is powering.

The PRM-6 Motor and Phase Rotation Tester can test the motor rotation of 3-phase systems, and verify 3-phase receptacle wiring and phase sequencing with test leads.

An additional advanced feature is wireless motor rotation detection, which senses motor rotation direction without use of test leads. This is particularly useful for fast-running motors when the motor rotation cannot be visually determined or when the drive shaft is not visible.

  • 3-phase wire sequence indication
  • Error displays (missing phase, one input connected to neutral or PE)
  • Non-contact, wireless motor rotation detection on running motors
  • Indicates motor rotation of disconnected motors when spinning the shaft by hand or other means
  • 3-phase to phase voltage up to 700 V
  • Clear backlit LCD display
  • Durable rubber casing for 3 ft. (1 m) drop proof protection
  • Safety: CAT IV 600 V

General Specifications

Operating temperature 0°C to 40°C (32°F to 104°C)
Operating altitude Up to 2000 m
Power AAA battery (2)
3 phase indication LCD
Dimensions (H x W x D) 5.43 in x 2.56 in x 1.3 in (13.7 cm x 6.5 cm x 3.3 cm)
Weight .38 lb (.17 kg) including battery
Dust/water resistance IP 40
Pollution degree 2
Overvoltage category CAT IV 600 V
Agency approvals CE
cCSAus
Safety Conforms to EN 61010-1
EN 61010-031
EN 61557-1
EN 61557-7
EMC Conforms to EN 61326-1

Electrical Specifications

Rotary field detection

Voltage range (frequency) 40 – 700 V (16 – 60 Hz)
50 – 700 V (60 – 400 Hz)
Nominal test current < 3.5 mA

Non-contract rotary field indication

Frequency range 16 - 400 Hz

Motor connection (with leads)

Voltage range ≥ 1 – 700 V
Frequency range 2 - 400 Hz
Nominal test current < 3.5 mA

Do you have a Phase Sequence and Motor Rotation Tester that needs to be calibrated?

We offer standard traceable calibration and ISO 17025 accredited calibration services.

Get your Phase Sequence and Motor Rotation Tester calibrated today! Click Here!