AMPROBE ALC-110 - Leakage Current Clamp
Overview
Features
Specifications
Calibration
Prevent unplanned downtime by detecting leakage currents with the ALC-110 Leakage Current
Clamp. Rated CAT III 600 V to ensure electrical safety, the ALC-110 is designed to resist external
magnetic fields for highly accurate readings.
Application
- Measure:
- Earth and differential leakage currents
- Leakage currents through the earth (PE) conductor
- Appliance current consumption without interruptions to the circuit
- Trace the source of earth leakage current
- Identify intermittent GFCI trips without switching equipment off
- Low influence of external magnetic fields
- True-rms measurements for accuracy when measuring complex, non-sinusoidal waveforms
- Mechanical jaw lock to assure accuracy of low current measurements 30 mm (1.2 in) jaw opening
- Highest resolution of 0.001 mA
- Measure up to 60 A
- Broad frequency range 15 Hz to 1 kHz for a variety of different applications
- Selectable filters:
- Low Pass 50/60Hz filter to perform measurements on equipment driven by Variable Frequency Drives (VFDs) or affected by high frequency noise
- Appliance Filter to conduct leakage current measurements on appliances
- No filter
- Selectable limits: 0.25 mA, 0.5 mA, 3.5 mA, 10 mA, 12 mA
- Max readings and hold function
- CAT III 600 V safety rating
General
Display | Digital: 6000 counts, updates 5/sec |
Range | Auto Ranging |
Over range indication | OL or -OL |
Operating temperature | 32 °F to 86 °F (0 °C to 30 °C), ≤ 80% RH 86 °F to 104 °F (30 °C to 40 °C), ≤ 75% RH 104 °F to 122 °F (40 °C to 50 °C), ≤ 45% RH |
Operating altitude | ≤ 2000 m |
Storage temperature | -4 °F to 140 °F (-20 °C to 60 °C) |
Pollution degree | 2 |
Temperature coefficient | 0.1 x (specified accuracy) / °C (<21 °C, <25 °C) |
Vibration requirement | acc. IEC 61557-1 clause 4.10 |
Drop proof | 4 ft (1.2 m) |
Battery | 2x batteries 1.5 V IEC LR03 AAA |
Battery life | 60 hours typical |
Safety compliance | IEC/EN 61010-1, IEC/EN 61010-2-030, IEC/EN 61010-2-032, IEC/EN 61557-13 |
EMC compliance | IEC/EN 61326-1, IEC/EN 61326-2-2 |
Dimensions (H x W x L) | 8.7 x 3.5 x 1.8 in (221 x 89 x 48 mm) |
Weight | 0.9 lb (410 g) with batteries installed |
Do you have a Leakage Current Clamp that needs to be calibrated?
We offer standard traceable calibration and ISO 17025 accredited calibration services.
Get your Leakage Current Clamp calibrated today! Click Here!
There are currently no reviews for this product.